DrägerSensor Dual IR Ex/CO2 UK
£0.00*
The DrägerSensor Dual IR Ex/CO2 precisely measures the concentration of flammable gases and carbon dioxide and warns of hazardous gas concentrations.
- Compatible with the Dräger X-am 5600 and Dräger X-am 8000
- The replaceable sensor comes with a one-year warranty and has an expected service life of more than 60 months
- Works on the principle of infrared absorption and remains capable of measuring even in oxygen-deficient or oxygen-free mixtures
- Fast response time in both diffusion and pump mode
Technical data – DrägerSensor Dual IR Ex/CO2
| Resolution | 1.0 % LEL for the Dräger X-am 5600 / X-am 8000 in the Ex measuring range; for CO2: 0.01 vol.% CO2 or 50 ppm CO2, depending on the measuring range |
|---|---|
| Measuring range | 0 to 100 % LEL or 0 to 100 vol.%, depending on the measured gas; CO2: 0 to 5 vol.% CO2 |
| Accuracy (sensitivity) |
|
| Long-term drift at 20 °C (68 °F) |
|
| Warm-up time | After a sensor replacement, approx. 3 minutes with the instrument switched on until calibration is possible |
| Environmental conditions |
|
| Effect of temperature |
|
| Effect of humidity |
|
Response time
| Mode | Dräger X-am 5600 | Dräger X-am 8000 |
|---|---|---|
| Diffusion mode t50 | ≤ 10 seconds | ≤ 10 seconds |
| Diffusion mode t90 | ≤ 15 seconds | ≤ 20 seconds |
| Pump mode t50 | ≤ 7 seconds | ≤ 10 seconds |
| Pump mode t90 | ≤ 10 seconds | ≤ 12 seconds |
Test gas: for Ex, 2.5 vol.% methane in air or 0.9 vol.% propane in air for the respective adjustment; for CO2, 2.0 vol.% CO2 in air. For safety-critical measurements, calibration and gas testing must be carried out in accordance with national regulations.
Relevant cross-sensitivities – DrägerSensor Dual IR Ex/CO2
The values given in the table are guide values and apply to new sensors. The values stated may vary by ±30%. The sensor may also be sensitive to other gases (data available from Dräger on request). Gas mixtures may be displayed as a combined total. Gases with a negative sensitivity can cancel out a positive Ex/CO2 reading. It should therefore be checked whether gas mixtures are present.
| Gas/vapour | Concentration | Reading in % LEL |
|---|---|---|
| Acetone | 1.25 vol.% | 18 |
| Benzene | 0.6 vol.% | 20 |
| 1,3-Butadiene | 0.7 vol.% | 20 |
| n-Butane | 0.7 vol.% | 42 |
| Ethanol | 1.55 vol.% | 41 |
| Propane | 0.85 vol.% | 50 |
Main areas of application
- Monitoring of hydrocarbons
- Monitoring of carbon dioxide
- Use in potentially explosive or safety-critical environments
- Industrial gas monitoring using infrared technology